Cables :
  XLPE insulated power cable for voltage up to 35KV

 



High Voltage Lab.


Brief Introduction to XLPE Insulated Power Cable

Cross-linked polyethylene insulated power cable not only has excellent electric, mechanical but also has powerful resistance against chemical corrosion, heataging and environmental stress. Its structure is simple. The permissible maximum operating temperature is 90”. It is convenient to use and can be laid with no restriction of different elevation.
Our XLPE cable can be produced according to our work's specification which is equivalent IEC60502, and its some properties required are superior to IEC60502.
We can design and manufacture special XLPE cable according to the other standards, required by the customers.

Rate
Voltage
KV
1st Class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd Class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
Number of core Cross section П
1 Core   1.5~800 25~800 25~1200 25~1200 35~1200 50~1200 50~1200 50~1200
2 Core   1.5~185 25~185            
3 Core   1.5~400 25~400 25~400 25~400 35~400 50~400 50~400 50~400
(3+1,4)
4 Core
  2.5~400 25~400            
(4+1,3_2,5)
5 Core
  2.5~400 25~400            
The cables in the 1st class are available to the condition of the earth fault time within 1 minute. The cables in the 2nd class are available to earth fault time not exceeding 2 hours generally, maximum time is not more than 8 hours


XLPE Cable's Type and Main Application
 
Type Description main Application
Cu core Al core
YJV
or
YJY
YJLV
or
YJLY
XLPE inslated, PVC or PE sheathed power cable For laying indoor, tunnel, canal and underground. Unable to bear external mechanical forces, but bear the traction force during laid
YJV22
or
YJV23
YJLV22
or
YJV23
XLPE insulated, steel tape armoured, PVC or PE sheathed power cable For laying indoor, tunnel, canal and underground, Able to bear external mechanical forces, but unable to bear large pulling force
YJV32
or
YJV33
YJLV32
or
YJLV33
XLPE insulated, fine steel wire armoured, PVC or PE sheathed power cable For laying in shaft, with large difference of level, able to bear external mechanical forces and moderate pulling force
YJV42
or
YJV43
YJLV42
or
YJLV43
XLPE insulated, thick steel wire armoured, PVC or PE sheathed power cable Able to bear positive pressure and pulling force
Note : "ZR-" undudes three kinds (A,B,C) of flame retardant cables, respectively indicated in "ZRA-", "ZRB-" or "ZRC-", For example, "ZRB-JYV", "ZRA-YJV22"


Cable Main Technical Characteristics

 
  : Conductor resistance of finished cable at 20” per kilometer is not more than the following
   values.
 
Normal
cross-section П
1.5 2.5 4 6 10 16 25 35 50 70
Cu Core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268
Al Core 18.1 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443

 

Normal
cross-section П
95 120 150 185 240 300 400 500 630 800
Cu Core 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Al Core 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 0.0367
 
   : B and C. Voltage Test and Partial Discharge Test

Rated Voltage Uo/Ukv

Item

0.6/1 1/1 1.8/3 3/3 3.6/6 6/6
6/10
8.7/10
8.7/15
12/20 18/20
18/30
21/35 26/35
B Voltage Test Test Voltage 3.5 4.5 6.5 9.5 11 15 22 30 45 53 65
Test Time 5 5 5 5 5 5 5 5 5 5 5
C Test of partial Discharge Test Voltage         6 9 13 18 27 32 39
Discharge Capacity         20 20 20 20 20 10 10

    
 