Power Cable Accessories :
  Terminations for Screen Paper Insulated Cables with one
  metal Sheath per Phase 20KV and 35KV

¡¡

¡¡

¡¡

COMPONENTS

1. Core
2. Lug
3. Red Mastic Filler
4. Sealing Insulation Tubing
5. Oil Barrier Sleeve
6. Anti-tracking Tubing
7. Stress Control Tubing
8. Glass Cushion Tape

 9. Belting Oil Barrier Sleeve
10. Worm Driver Clamp
11. Earthing Plumb
12. Earthing Braid
13. Adhesive Lined Gland Sleeve
14. Protection Umbrella
15. Single-core Skirt
16. Perorated Metal Foil Screen
17. Breakout

Cables
  • The terminations are designed for 1-and 3-core screen paper insulated cables with one metal sheath per phase.
    For Example : ZQFD41, ZQFD20, NAEKEBA, NEKENA, NEKEBY.

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140103070110 NSZ 35 / 1x1 35KV 1-core PILC cable indoor termination 25-50
4140103070120 NSZ35 / 1x2 70-120
4140103070130 NSZ35 / 1x3 150-240
4140103070140 NSZ35 / 1x4 300-400
4140103080110 WSZ 35 / 1x1 35KV 1-core PILX cable outdoor termination 25-50
4140103080120 WSZ35 / 1x2 70-120
4140103080130 WSZ35 / 1x3 150-240
4140103080140 WSZ 35 / 1x4 300-400
4140103100110 NSZ 35 / 3x1 35KV 3-core PILX cable indoor termination 25-50
4140103100120 NSZ35 / 3x2 70-120
4140103100130 NSZ35 / 3x3 150-240
4140103100140 NSZ35 / 3x4 300-400
4140103110110 WSZ 35 / 3x1 35KV 3-core PILX cable outdoor termination 25-50
4140103110120 WSZ35 / 3x2 70-120
4140103110130 WSZ35 / 3x3 150-240
4140103110140 WSZ35 / 3x4 300-400
¡¡

Heat-shrink Power Cable Accessories Testing for 35KV PILC Cable
¡¡
Item
NO
property Test Requirements Results Outdoor termination Indoor termination
1 AC withstand for 1min
(dry withstand)
GB11033 No breakdown and flashover shall occur at 105kv No breakdown and flashover occurred on the combi.sample at 105kv, 1min ¡¡ OK
2 AC withstand for 1min
(wet withstand)
GB11033 No breakdown and flashover shall occur at 105kv No breakdown and flashover occurred on the combi.sample at 105kv, 1min OK OK
3 Load cycle GB11033 Heating for 5h, cooling for 3h, Conductor¡¯s temperature is 65¡É, 3cycles Conductor¡¯s temperture is 65¡É.Results refer to the following Test As left As left
4 Impulse Voltage withstand 1.2/50us¡¾10times GB11033 10positive and 10 negative impulses at 250KV, Flashover 1time is allowed but not including total testing times 10 positive and 10 negative impulses at 250KV,No breakdown of the combi.sample occurred at 250KV OK OK
5 DC Voltage withstand, negative 15min GB11033 No breakdown and flashover shall occur at 156kv No breakdown and flashover occurred on the combi.sample at 156kv, 15min OK OK
6 AC Voltage withstand, 4h GB11033 No breakdown and flashover shall occur at 104kv No breakdown and flashover occurred on the combi.sample at 104kv, 4min OK OK
7 Oil-seal up test DL413 Heating for 24h, cooling for 24h, Conductor¡¯s temperature is 65¡É, oil pressure : 100MPa Heating for 24h, cooling for 24h, Conductor¡¯s temperature is 65¡É, oil pressure : 100MPa,No leaking, No seeping OK OK

    
¡¡